Title :
Dynamic loading of distribution transformers from models of dynamic thermal
Author :
Francisco Aldinei Pereira Aragão;Sérgio dos Santos Lima;Otacílio M. Almeida;Arthur Plínio de Souza Braga;Kathiane Queiroz da Silva;Reginaldo Silva dos Anjos
Abstract :
It is known that to monitor intrinsic life of transformers variables has been the object of concern in regard to avoid economic losses caused by faults in such equipment. It is possible through the system management, maximize the lifetime and improve grid reliability, which could also reduce maintenance costs. This paper brings a contribution to the development of these systems by proposing and testing a model based on the enhancement of IEEE standard for modeling the top oil and the hot spot temperature of distribution transformers of Manaus Energia Utility to establish maximum loading limits for the equipment that minimize the loss of lifetime. The results were compared with a standard IEEE model, which presented more conservative results.
Keywords :
"Oil insulation","Power transformer insulation","Mathematical model","Loading","Load modeling","Temperature measurement"
Conference_Titel :
Industry Applications (INDUSCON), 2010 9th IEEE/IAS International Conference on
Print_ISBN :
978-1-4244-8008-1
DOI :
10.1109/INDUSCON.2010.5740062