DocumentCode :
3650355
Title :
A transient based approach to diagnose high impedance faults on smart distribution networks
Author :
F. V. Lopes;W. C. Santos;D. Fernandes;W. L. A. Neves;N. S. D. Brito;B. A. Souza
Author_Institution :
Federal University of Campina Grande (UFCG), 882 Apr?gio Veloso Av., Bodocong? 58.429-900, Campina Grande, PB, Brazil
fYear :
2013
fDate :
4/1/2013 12:00:00 AM
Firstpage :
1
Lastpage :
8
Abstract :
This paper presents a transient based approach to diagnose high impedance faults (HIFs) on smart distribution grids. The algorithm does not require the knowledge of the feeder parameters and uses the discrete wavelet transform (DWT) to monitor fault-induced transients at strategic points of the power system, taking advantages of available Smart Grid communication channels. It allows the HIF detection and then the identification of the area in which the fault occurred. The proposed methodology is evaluated through Electromagnetic Transients Program (EMTP) simulations of HIFs in a 13.8 kV system, which was modeled using actual data of a Brazilian distribution network. Obtained results show that the method is able to detect HIFs practically at the disturbance inception as well as to provide a great reduction of the fault search field using a small computational burden.
Keywords :
"Transient analysis","Monitoring","Discrete wavelet transforms","Smart grids","Impedance","Fault detection"
Publisher :
ieee
Conference_Titel :
Innovative Smart Grid Technologies Latin America (ISGT LA), 2013 IEEE PES Conference On
Print_ISBN :
978-1-4673-5272-7
Type :
conf
DOI :
10.1109/ISGT-LA.2013.6554450
Filename :
6554450
Link To Document :
بازگشت