Title :
Starting of diesel electrical aggregate loaded with an induction motor
Author :
R. Erceg;G. Erceg;S. Tesnjak
Author_Institution :
Dept. of Power Syst., Zagreb Univ., Croatia
Abstract :
Switching larger induction motors on the buses of a diesel electrical aggregate causes large voltage and frequency drops. Also, it can cause severe disturbances to any locally connected loads on the aggregate´s buses. In this paper, a method of starting an induction motor, loaded on the aggregate, by simultaneously changing voltage and frequency is presented. Besides the mathematical model of the diesel electrical aggregate, a mathematical model of the induction motor is also given. Results obtained with simulation are compared with experimental results obtained from a laboratory model. With this method, the starting of larger induction motors can be realized without using special starters (soft start).
Keywords :
"Aggregates","Induction motors","Capacitors","Surges","Voltage fluctuations","Torque","Power systems","Voltage control","Frequency","Resistors"
Conference_Titel :
Industrial Electronics Society, 1998. IECON ´98. Proceedings of the 24th Annual Conference of the IEEE
Print_ISBN :
0-7803-4503-7
DOI :
10.1109/IECON.1998.724174