DocumentCode
3656750
Title
Design guidelines for safer low-voltage distribution systems Part II: Motor circuits
Author
Gary H. Fox
Author_Institution
Gen. Electr., Concord, CA, USA
fYear
2015
fDate
5/1/2015 12:00:00 AM
Firstpage
1
Lastpage
8
Abstract
This paper continues investigations of the concept of maximum low voltage circuit breaker ratings that facilitate fast tripping for arcing faults with a selectively coordinated system. Motor loads are the focal point of the report. Guidelines are provided for maximum motor horsepower ratings that should be used depending on the kVA rating of the suppy-side transformer. Using the guidelines should prevent a situation from occurring where the coordinated main circuit breaker short time and instantanesous settings are not sensitive enough to detect main bus arcing currents, and dangerous levels of arc incident energy are possible.
Keywords
"Relays","Switches","Standards","Guidelines"
Publisher
ieee
Conference_Titel
Industrial & Commercial Power Systems Technical Conference (I&CPS), 2015 IEEE/IAS 51st
Type
conf
DOI
10.1109/ICPS.2015.7266441
Filename
7266441
Link To Document