DocumentCode :
3662110
Title :
Hybrid topology and PRD controller applied in three-phase system based on induction generator
Author :
Celso B. Tischer;Lucas G. Scherer;Jonas R. Tibola;Robinson F. de Camargo
Author_Institution :
Power Electronics and Control Group - GEPOC, Federal University of Santa Maria - UFSM, RS - Brazil
fYear :
2015
fDate :
6/1/2015 12:00:00 AM
Firstpage :
512
Lastpage :
517
Abstract :
This paper deals with a control system for voltage regulation in stand-alone generation systems based on self-excited induction generators (SEIG). It is considered a three-wire hybrid topology composed by switchable capacitor banks and distribution static compensator (DSTATCOM). While the switchable capacitor banks supply the most part of the reactive power for voltage regulation, the DSTATCOM is controlled in order to supply the difference of reactive power, balance induction generation (IG) currents and compensate harmonics of load currents. To accomplish that, it is proposed the use of proportional-resonant-derivative (PRD) controllers in association to proportional-integral (PI) controllers to control the compensation currents processed by DSTATCOM. The proposed method of voltage regulation using DSTATCOM-switchable capacitors is implemented on an IG prototype system and the test results are presented to demonstrate its performance.
Keywords :
"Capacitors","Reactive power","Voltage control","Switches","Topology","Capacitance"
Publisher :
ieee
Conference_Titel :
Industrial Electronics (ISIE), 2015 IEEE 24th International Symposium on
Electronic_ISBN :
2163-5145
Type :
conf
DOI :
10.1109/ISIE.2015.7281520
Filename :
7281520
Link To Document :
بازگشت