DocumentCode
3664396
Title
The application of multi-sensor technique in switchgear partial discharge precise location
Author
Peng Kong;Lin Wang;Zhen Li;Yiming Zhang;Yongpeng Xu
Author_Institution
State Grid Liaocheng Power Supply Company, Liaocheng 252000, China
fYear
2015
fDate
5/1/2015 12:00:00 AM
Firstpage
337
Lastpage
340
Abstract
This paper describes the basic theory and detection methods of UHF, ultrasonic and high-frequency on-site detection. With the example of failed switchgear on-site detection in 35kV substation, this paper analyzes the application of multi-sensor partial discharge detection technique in the area of switchgear insulation defects detection. Combined with the on-site analysis and disassembled maintenance, the paper verifies the switchgear detection and location´s feasibility and accuracy of multi-sensors technique.
Keywords
"Partial discharges","Switchgear","Acoustics","Discharges (electric)","Insulation","Fault location"
Publisher
ieee
Conference_Titel
Electronics Information and Emergency Communication (ICEIEC), 2015 5th International Conference on
Print_ISBN
978-1-4799-7283-8
Type
conf
DOI
10.1109/ICEIEC.2015.7284553
Filename
7284553
Link To Document