DocumentCode
3664397
Title
The development of transducer to detect partial discharge in XLPE cable based on electromagnetic coupling method
Author
Xiaoli Hu;Yubing Duan;Xinyan Feng;Jun Yong;Bo Yang;Minglin Liu;Hailei Meng;Xiaobin Sun;Yiming Zhang
Author_Institution
Shandong Elecrtic Power Research Institute, Ji´nan 250002, China
fYear
2015
fDate
5/1/2015 12:00:00 AM
Firstpage
341
Lastpage
344
Abstract
The partial discharge is an important parameter to reflect the insulation condition of XLPE power cable. The electromagnetic coupling method is the most effective method to detect partial discharge in XLPE cable. Based on the electromagnetic coupling means, this paper designs and develops a kind of transducer to detect partial discharge in XLPE cable. According to the choice of the appropriate core material characteristic of partial discharge signal, a serial of model analysis and test have been performed to determine the integrating resistance and coiling number´s influence on amplitude-frequency characteristics of current transducer. The key parameters of the optimal integral resistance and the number of windings of the coil sensor is determined. The test in laboratory and the installation in the field have proved that the transducer has wide working frequency band and high sensitivity which meets the request of XLPE cable partial discharge detection.
Keywords
"Transducers","Partial discharges","Power cables","Magnetic cores","Windings","Power cable insulation"
Publisher
ieee
Conference_Titel
Electronics Information and Emergency Communication (ICEIEC), 2015 5th International Conference on
Print_ISBN
978-1-4799-7283-8
Type
conf
DOI
10.1109/ICEIEC.2015.7284554
Filename
7284554
Link To Document