DocumentCode :
3665291
Title :
Estimating dynamic model parameters for adaptive protection and control in power system
Author :
Ariff Mam;Bikash Pal;Abhinav Singh
Author_Institution :
Electrical, Imperial College London, U. K.
fYear :
2015
fDate :
7/1/2015 12:00:00 AM
Firstpage :
1
Lastpage :
1
Abstract :
Summary form only given. This paper presents a new approach in estimating important parameters of power system transient stability model such as inertia constant $H$ and direct axis transient reactance $x_{d}^{prime}$ in real time. It uses a variation of unscented Kalman filter (UKF) on the phasor measurement unit (PMU) data. The accurate estimation of these parameters is very important for assessing the stability and tuning the adaptive protection system on power swing relays. The effectiveness of the method is demonstrated in a simulated data from 16-machine 68-bus system model. The paper also presents the performance comparison between the UKF and EKF method in estimating the parameters. The robustness of method is further validated in the presence of noise that is likely to be in the PMU data in reality.
Keywords :
"Adaptation models","Power system stability","Phasor measurement units","Adaptive systems","Power system transients","Stability analysis","Power system dynamics"
Publisher :
ieee
Conference_Titel :
Power & Energy Society General Meeting, 2015 IEEE
ISSN :
1932-5517
Type :
conf
DOI :
10.1109/PESGM.2015.7285733
Filename :
7285733