• DocumentCode
    3665532
  • Title

    Transient Stability Assessment of power systems through Wide-Area Monitoring System

  • Author

    Matin Rahmatian;William G. Dunford;Atefeh Palizban;Ali Moshref

  • Author_Institution
    Department of Electrical and Computer Engineering, University of British Columbia, Vancouver, Canada
  • fYear
    2015
  • fDate
    7/1/2015 12:00:00 AM
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Real-time transient stability assessment is becoming more feasible using synchrophasor systems. Modern Wide-Area Monitoring Systems (WAMS) are equipped with PMUs and fast communication infrastructure. The paramount advantage of modern WAMS is their capability to provide fast, reliable and synchronized real-time measurements of different system parameters. In this paper, a new real-time Transmission Stability Assessment (TSA) technique is proposed. In the proposed technique, angle-based indices are applied to train five consecutive Decision Trees (DTs) which are used for real-time TSA. The proposed technique is tested on the Northern Intertie, connecting BC Hydro and Bonneville Power Administration (BPA) systems. The obtained results validate the efficiency of the proposed scheme.
  • Keywords
    "Power system stability","Stability criteria","Transient analysis","Synchronization","Indexes","Power generation"
  • Publisher
    ieee
  • Conference_Titel
    Power & Energy Society General Meeting, 2015 IEEE
  • ISSN
    1932-5517
  • Type

    conf

  • DOI
    10.1109/PESGM.2015.7285984
  • Filename
    7285984