DocumentCode :
3665657
Title :
The need for a new generation of var meters
Author :
Tan Zhang;John A. Orr;Alexander E. Emanuel
Author_Institution :
Department of Electrical and Computer Engineering, Worcester, MA 01609, USA
fYear :
2015
fDate :
7/1/2015 12:00:00 AM
Firstpage :
1
Lastpage :
5
Abstract :
This study extends previous work on the appropriate definition of reactive power in the presence of harmonic voltages and currents to the three-phase, unbalanced case. As in the single phase case, it is advocated that reactive power be defined in terms of the fundamental components (60/50 Hz) of the current and the phase angle separating them. It is demonstrated that common metering techniques for reactive power in the presence of harmonics yield inaccurate results, with errors as great as 200%. Modern digital instrumentation is able to conveniently calculate correct values so the time has arrived to start improvements in the design of a new generation of var meters through comprehensive implementation of these digital techniques.
Keywords :
"Reactive power","Harmonic analysis","Power measurement","Voltage measurement","Power system harmonics","Current measurement"
Publisher :
ieee
Conference_Titel :
Power & Energy Society General Meeting, 2015 IEEE
ISSN :
1932-5517
Type :
conf
DOI :
10.1109/PESGM.2015.7286119
Filename :
7286119
Link To Document :
بازگشت