Least squares estimation-based synchronous generator parameter estimation using PMU data
Author
Bander Mogharbel;Lingling Fan;Zhixin Miao
Author_Institution
Smart Grid Power Systems Lab at EE Dept of University of South Florida, USA
fYear
2015
fDate
7/1/2015 12:00:00 AM
Firstpage
1
Lastpage
5
Abstract
In this paper, least square estimation (LSE)-based dynamic generator model parameter identification is investigated. Electromechanical dynamics related parameters such as inertia constant and primary frequency control droop for a synchronous generator are estimated using Phasor Measurement Unit (PMU) data obtained at the generator terminal bus. The key idea of applying LSE for dynamic parameter estimation is to have a discrete autoregression with exogenous input (ARX) model. With an ARX model, a linear estimation problem can be formulated and the parameters of the ARX model can be found. This paper gives the detailed derivation of converting a generator model with primary frequency control into an ARX model. The generator parameters will be recovered from the estimated ARX model parameters afterwards. Two types of conversion methods are presented: zero-order hold (ZOH) method and Tustin method. Numerical results are presented to illustrate the proposed LSE application in dynamic system parameter identification using PMU data.
Keywords
"Mathematical model","Numerical models","Phasor measurement units","Power system dynamics","Generators","Transfer functions","Estimation"
Publisher
ieee
Conference_Titel
Power & Energy Society General Meeting, 2015 IEEE
ISSN
1932-5517
Type
conf
DOI
10.1109/PESGM.2015.7286559
Filename
7286559
Link To Document