    Improvement of on-line monitoring method for insulation of substation DC system

  • Author

    Lei Xing;Xu Nan;Shen Wei;Dai Chunyi;Xu Zhaode

  • Author_Institution
    Maintenance Company, Shanghai Municipal Electric Power Company, Shanghai, China
  • fYear
    2015
  • fDate
    6/1/2015 12:00:00 AM
  • Firstpage
    1350
  • Lastpage
    1355
  • Abstract
    When patrolling process of substation DC grounding offer a plurality of suspected branch faults, the existences of influence factors such as zero drift, transformer remanence, and transformer stability, impact on the efficiency of grounding troubleshooting, leading to wrong selection or missed selection. According to the logical relationship of state variables such as voltage, current and calculated value such as grounding resistance before and after the fault, the causes of wrong selection or missed selection are analyzed, the characteristics of the faults are identified based on circuit schematic, the calculation process of grounding resistance is checked, automatic inspection mode based on logic event driven is proposed, not only to improve the accuracy of DC lookup, but also to identify the branch with zero drift.
  • Keywords
    "Resistance","Grounding","Leakage currents","Bridge circuits","Insulation","Electrical resistance measurement","Voltage measurement"