DocumentCode :
3666819
Title :
Improvement of on-line monitoring method for insulation of substation DC system
Author :
Lei Xing;Xu Nan;Shen Wei;Dai Chunyi;Xu Zhaode
Author_Institution :
Maintenance Company, Shanghai Municipal Electric Power Company, Shanghai, China
fYear :
2015
fDate :
6/1/2015 12:00:00 AM
Firstpage :
1350
Lastpage :
1355
Abstract :
When patrolling process of substation DC grounding offer a plurality of suspected branch faults, the existences of influence factors such as zero drift, transformer remanence, and transformer stability, impact on the efficiency of grounding troubleshooting, leading to wrong selection or missed selection. According to the logical relationship of state variables such as voltage, current and calculated value such as grounding resistance before and after the fault, the causes of wrong selection or missed selection are analyzed, the characteristics of the faults are identified based on circuit schematic, the calculation process of grounding resistance is checked, automatic inspection mode based on logic event driven is proposed, not only to improve the accuracy of DC lookup, but also to identify the branch with zero drift.
Keywords :
"Resistance","Grounding","Leakage currents","Bridge circuits","Insulation","Electrical resistance measurement","Voltage measurement"
Publisher :
ieee
Conference_Titel :
Cyber Technology in Automation, Control, and Intelligent Systems (CYBER), 2015 IEEE International Conference on
Print_ISBN :
978-1-4799-8728-3
Type :
conf
DOI :
10.1109/CYBER.2015.7288140
Filename :
7288140