DocumentCode
3669977
Title
The research of 110kV transmission line expanding diameter insulation jacket
Author
Yang Jin;Bo Zhang;Mingyu Sun;Weiqun Lei;Xiaoquan Zheng;Jiang Wu
Author_Institution
State Key Laboratory Of Electrical Insulation And Power Equipment, Xi´an, China
fYear
2015
fDate
7/1/2015 12:00:00 AM
Firstpage
468
Lastpage
471
Abstract
To eliminate local corona and reduce minimal discharge distance of transmission lines, this paper analyzed expanding diameter insulation jacket for 110kV transmission line. The minimal discharge distance and its relationship with the diameter of semi-conducting and expanding diameter was calculated theoretically, finding the best size of expanding diameter and general standard of expanding diameter jacket. Then a model of 110kV bare conductor installing expanding diameter insulation jacket is built, to figure out its electric field distribution by finite element method. Through analyzing, expanding diameter insulation jacket proved to be effective, and its minimal discharge distance decreases 60%.
Keywords
"Insulation","Conductors","Discharges (electric)","Grounding","Power transmission lines","Surface discharges","Mathematical model"
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials (ICPADM), 2015 IEEE 11th International Conference on the
Electronic_ISBN
2160-9241
Type
conf
DOI
10.1109/ICPADM.2015.7295310
Filename
7295310
Link To Document