Title :
Relationship between carbonized traces and space charges in oil-paper insulation
Author :
Feiran Li;Yangchun Cheng;Xiao Tian;Botao Duan;Chunhe Cheng;Zijian Zhao
Author_Institution :
State Key Laboratory of Alternate Electrical Power System with Renewable Energy, North China Electric Power University, Beijing 102206, China
fYear :
2015
fDate :
7/1/2015 12:00:00 AM
Firstpage :
971
Lastpage :
974
Abstract :
Among all the types of transformer insulation deterioration, partial discharge is relatively a direct one that may lead to carbon traces which have negative effect on insulation. We believe that the relationship between the trace length and total appearance charge of partial discharges is a key to diagnose the oil paper insulation´s remained life, even though the carbon trace in paper or pressboard cannot be seen directly like the transparent material such as XLPE. In this paper, we put forward an electrical method based on the hypothesis that the space charges just stay where the partial discharge happened before. Based on a distributed potential measuring system, we pay attention to carbon traces developed in a single electrical tree. After a series of high voltage experiments, we calculate the position of the space charges by their electric field and then we get the trace length by the farthest space charges. Finally, we get the result of experiment consisted with that of the theory calculations.
Keywords :
"Partial discharges","Carbon","Space charge","Oil insulation","Power transformer insulation","Strips"
Publisher :
ieee
Conference_Titel :
Properties and Applications of Dielectric Materials (ICPADM), 2015 IEEE 11th International Conference on the
Electronic_ISBN :
2160-9241
Type :
conf
DOI :
10.1109/ICPADM.2015.7295436