• DocumentCode
    3671333
  • Title

    Frequency and time domain calibration for large Rogowski coils

  • Author

    S. L. Combrink;P. G. Wiid

  • Author_Institution
    Department Electrical and Electronical Engineering, Stellenbosch University, Cnr of Banghoek&
  • fYear
    2015
  • Firstpage
    989
  • Lastpage
    992
  • Abstract
    The SKA needs strong mitigation measures to ensure a radio quiet environment. In an ongoing study, lightning induced RFI is investigated as well as a means to measure and mitigate its effects. The Rogowski coil is chosen as the principle current transducer and its calibration is studied. A time domain calibration approach is investigated and verified with a commercial current probe´s calibration data. This approach along with larger Rogowski coils requires an enlarged fixture for calibration. The larger fixtures introduce a mismatch resulting in high reflection loss. Simulations show that by using a dielectric with high permittivity in the calibration fixture a smaller fixture is realisable.
  • Keywords
    "Calibration","Coils","Probes","Current measurement","Conductors","Impedance","Bandwidth"
  • Publisher
    ieee
  • Conference_Titel
    Electromagnetics in Advanced Applications (ICEAA), 2015 International Conference on
  • Type

    conf

  • DOI
    10.1109/ICEAA.2015.7297263
  • Filename
    7297263