DocumentCode :
3679053
Title :
Comparison of losses in different topologies of step-up/step-down inverters
Author :
L. Hernandez;T. Meynard;A. Lacarnoy
Author_Institution :
Schneider Electric, 140, Av Jean Kuntzmann, 38334 St ISMIER, France
fYear :
2015
Firstpage :
1
Lastpage :
10
Abstract :
Standard Voltage Source Inverters (VSI) operates with a DC voltage source greater than the peak voltage of the AC source and Current Source Inverters (CSI) with a DC voltage source lower than the peak voltage of the AC source. This paper shows how several topologies of reversible AC/DC buck-boost inverters which do not suffer from such constraints can be compared on the basis of semiconductor and inductor losses. The main quantities in these converters, such as average current, RMS current, etc. are derived from an analytical analysis and they are combined to semiconductor loss models to derive losses and efficiency of each topology for different working conditions.
Keywords :
"Inverters","Topology","Uninterruptible power systems","Choppers (circuits)","Batteries","Insulated gate bipolar transistors","Switches"
Publisher :
ieee
Conference_Titel :
Power Electronics and Applications (EPE´15 ECCE-Europe), 2015 17th European Conference on
Type :
conf
DOI :
10.1109/EPE.2015.7309442
Filename :
7309442
Link To Document :