• DocumentCode
    3679433
  • Title

    Sensitive load voltage compensation with a suitable control method

  • Author

    Darlan A. Fernandes;Fabiano F. Costa;João R. S. Martins;Alberto S. Lock;Edison R. C. da Silva;Montiê A. Vitorino

  • Author_Institution
    Department of Electrical Engineering, Federal University of Paraí
  • fYear
    2015
  • Firstpage
    1639
  • Lastpage
    1644
  • Abstract
    This work proposes the usage of a repetitive-based control to dynamically restore the voltage applied to grid sensitive loads. The control is able to wipe off harmonic distortion and relies on simple transfer function. As a consequence, there is no need to apply harmonic selective filters. Moreover, the filter is able to work on sinusoid references and avoids employment of the dq transform. The design of the control parameters along with the system stability are discussed. A Simulink-based simulation has been built to verify the designed control performance. The experimental results are extracted from a setup of three-phase compensator which copes correctly with different scenarios of sagged and harmonic distorted voltages.
  • Keywords
    "Voltage control","Control systems","Harmonic analysis","Voltage fluctuations","Transfer functions","Harmonic distortion","Power system stability"
  • Publisher
    ieee
  • Conference_Titel
    Energy Conversion Congress and Exposition (ECCE), 2015 IEEE
  • ISSN
    2329-3721
  • Electronic_ISBN
    2329-3748
  • Type

    conf

  • DOI
    10.1109/ECCE.2015.7309891
  • Filename
    7309891