DocumentCode :
3679752
Title :
Condition monitoring and winding fault detection of inductors in LCL filter integrated with active front end rectifier
Author :
A Subash Chandar;Sanjib Kumar Panda;Sivakumar Nadarajan;Amit Kumar Gupta
Author_Institution :
Electrical and Computer Engineering, National University of Singapore Singapore 117583
fYear :
2015
Firstpage :
3922
Lastpage :
3927
Abstract :
This paper presents an online Condition Monitoring (CM) methodology for inductors in LCL filter integrated with Active Front End Rectifier (AFER). The proposed methodology monitors the winding flux of each phase of grid side and converter side inductors and compares with the winding flux under healthy condition to detect and identify the winding fault. The developed technique uses the Fast Fourier Transform (FFT) to extract the magnitude of the fundamental component of the winding flux. Hence, low bandwidth magnetic flux sensors integrated with a simple FFT algorithm can be used to detect and localize the winding fault. The effectiveness of the fault detection methodology has been analyzed and studied using the developed mathematical and FEM model. The proposed methodology has been tested on a laboratory prototype of 1.4 kVAr inductor at different input voltages and short circuit resistances. Both simulation and experimental results are found to validate the proposed fault detection methodology.
Keywords :
"Inductors","Windings","Magnetic flux","Integrated circuit modeling","Mathematical model","Magnetic fields","Power harmonic filters"
Publisher :
ieee
Conference_Titel :
Energy Conversion Congress and Exposition (ECCE), 2015 IEEE
ISSN :
2329-3721
Electronic_ISBN :
2329-3748
Type :
conf
DOI :
10.1109/ECCE.2015.7310214
Filename :
7310214
Link To Document :