DocumentCode
3682387
Title
Comparison of contact measurement and free-space radiation measurement of partial discharge signals
Author
A Jaber;P Lazaridis;Y Zhang;D Upton;H Ahmed;U Khan;B Saeed;P Mather;M F Q Vieira;R Atkinson;M Judd;I A Glover
Author_Institution
Department of Engineering &
fYear
2015
Firstpage
1
Lastpage
4
Abstract
Two partial discharge (PD) measurement techniques, a contact measurement technique (similar to the IEC 60270 standard measurement) and a free-space radiation (FSR) measurement technique, are compared for the case of a floating electrode PD source. The discharge pulse shapes and PD characteristics under high voltage DC conditions are obtained. A comparison shows greater similarity between the two measurements than was expected. It is inferred that the dominant mechanism in shaping the spectrum is the band-limiting effect of the radiating structure rather than band limiting by the receiving antenna. The cumulative energies of PD pulses in both frequency and time domains are also considered.
Keywords
"Partial discharges","Frequency measurement","Partial discharge measurement","Antenna measurements","Charge measurement","Radio frequency","Insulation"
Publisher
ieee
Conference_Titel
Automation and Computing (ICAC), 2015 21st International Conference on
Type
conf
DOI
10.1109/IConAC.2015.7313955
Filename
7313955