DocumentCode
3686401
Title
An online controller redesign based fault-tolerant strategy for thermal comfort in a multi-zone building
Author
Joseph J. Yame;Tushar Jain;Dominique Sauter
Author_Institution
Uni-versité
fYear
2015
Firstpage
1901
Lastpage
1906
Abstract
Variable air volume (VAV) boxes are used in multi-zone buildings, which varies the volume of constant temperature air separately supplied by an air-handling unit to meet challenging thermal load demands of individual zones. A fault appearing in the VAV damper severely affects the control performance and consequently, the energy efficiency of the overall system. To address this issue, we present a novel online redesign based fault-tolerant control strategy in this paper for a VAV thermal system in a multi-zone building. The novelty of the proposed strategy is that no a priori information about the process is used in real-time. In fact, no online identification of the thermal dynamical model of the building process or estimation of its operating status (healthy or faulty) is done. The design of the fault accommodation scheme is solely based on the real-time trajectories generated by the process. In order to demonstrate the effectiveness of the developed strategy, we consider a case-study of three-zones in a one-story building.
Keywords
"Buildings","Shock absorbers","Polynomials","Fault tolerance","Fault tolerant systems","Trajectory"
Publisher
ieee
Conference_Titel
Control Applications (CCA), 2015 IEEE Conference on
Type
conf
DOI
10.1109/CCA.2015.7320887
Filename
7320887