Title :
Procedure for protection of distribution feeder against induced voltages by indirect lightning
Author :
M. A. Araújo;R. A. Flauzino;O. E. Batista;L. A. Moraes
Author_Institution :
Department of Electrical and Computer Engineering, University of Sã
Abstract :
Induced voltages by indirect lightning cause faults, damage to equipment and malfunctions to electric power systems, compromising the quality, continuity and reliability of the electrical energy supply. In this context, research development is crucial to improve lightning protection procedures, especially for electrical systems located in areas with high ground flash densities. This article presents the results of the application of a practical procedure for protection of the IEEE 13 Node Test Feeder against induced voltages by indirect lightning simulated with the Rusck model employing metal-oxide surge arresters. The results demonstrate the efficiency and practicality of the presented procedure regarding the technical specification and definition of the best allocation and amount of surge arresters for feeder protection, as well as the analysis of the sensitivity of the transformers and load facing the induced voltages.
Keywords :
"Surges","Lightning","Arresters","Load modeling","Data models","Discharges (electric)"
Conference_Titel :
Lightning Protection (XIII SIPDA), 2015 International Symposium on
DOI :
10.1109/SIPDA.2015.7339270