DocumentCode
3699380
Title
Calculation of lightning transient voltages in cables considering a large industrial site using a FDTD thin wire model
Author
Luis Diaz;Celine Miry;Christophe Guiffaut;Nicolas Ticaud;Alain Reineix
Author_Institution
Laboratoire de Maté
fYear
2015
Firstpage
197
Lastpage
203
Abstract
An efficient model to include thin wire structures in FDTD is used and validated in a lightning transient study on a buried cable in a realistic industrial site. The model is based on the thin wire formalism of Holland and permits to consider different types of structures: bare wires, single core insulated cables, and single core coaxial cables. The industrial site is composed by a building, a grounding grid, and a buried single core coaxial cable leaving the building. An equivalent electronic equipment is connected to the extremities of the core. A lightning strikes the building, and the currents along the cable (shield and core), as well as the voltage at the extremes are examined. The results were compared with a MoM numerical tool, with good agreement and a significant better performance in terms of computational resources.
Keywords
"Wires","Coaxial cables","Cable shielding","Mathematical model","Buildings","Finite difference methods","Cable insulation"
Publisher
ieee
Conference_Titel
Lightning Protection (XIII SIPDA), 2015 International Symposium on
Type
conf
DOI
10.1109/SIPDA.2015.7339312
Filename
7339312
Link To Document