DocumentCode :
3699505
Title :
Performance evaluation of a four terminal HVDC systems for multi-directional power flow
Author :
Roberto Sandano;Malabika Basu;Michael Farrell;Michael Conlon
Author_Institution :
Unipd, Italy
fYear :
2015
Firstpage :
1
Lastpage :
4
Abstract :
This paper presents a configuration of multi-terminal VSC-HVDC transmission system, suitable for large offshore wind farms. The chosen multi-terminal arrangement consists of four terminals of which there are two wind farms, and the rest two are grid connections that can absorb different power, based on pre-arranged master-slave agreement (Fig.1). Various power flow conditions between grid terminals are tested to show the VSC reverse power capability of each grid side terminal. Strongly varied wind condition are tested, to evaluate the overall stability of the MTDC system. Adopted direct control system, in configuration with DC slack bus, is studied to avoid fast communication devices between the all terminals. The operation of the multi-terminal HVDC transmission system is examined through simulations using MATLAB®-SIMULINK®.
Keywords :
"Power conversion","Voltage control","HVDC transmission","Load flow","Reactive power","Wind farms"
Publisher :
ieee
Conference_Titel :
Power Engineering Conference (UPEC), 2015 50th International Universities
Type :
conf
DOI :
10.1109/UPEC.2015.7339851
Filename :
7339851
Link To Document :