• DocumentCode
    3711448
  • Title

    Field demonstration of using advanced PV inverter functionality to mitigate the impacts of high-penetration PV grid integration on the distribution system

  • Author

    Barry Mather;Araya Gebeyehu

  • Author_Institution
    National Renewable Energy Laboratory, Golden, CO, 80401, USA
  • fYear
    2015
  • fDate
    6/1/2015 12:00:00 AM
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper describes a field demonstration that was completed to show the ability of currently installed PV inverters to implement advanced PV inverter functionality and that such functionality was effective at reducing the voltage-related PV impacts of high-penetration PV integration. A distribution circuit was instrumented and then tested for a two week period using off-unity power factor operation. Specifically, an inductive power factor of -0.95 was demonstrated. The results show that the PV inverters were capable of such operation and that the use of off-unity power factor operation was highly effective at reducing the voltage-related impacts of the PV systems interconnected to the circuits used in the demonstration. The impacts of using off-unity power factor operation - resulting in additional reactive current flow on the distribution circuit - are also presented and analyzed.
  • Keywords
    "Inverters","Substations"
  • Publisher
    ieee
  • Conference_Titel
    Photovoltaic Specialist Conference (PVSC), 2015 IEEE 42nd
  • Type

    conf

  • DOI
    10.1109/PVSC.2015.7356169
  • Filename
    7356169