• DocumentCode
    3712166
  • Title

    Electrical model of building structures under ground-fault conditions. Part II

  • Author

    Fabio Freschi;Massimo Mitolo;Riccardo Tommasini

  • Author_Institution
    Politecnico di Torino, Corso Duca degli Abruzzi, 24, 10129 Torino (Italy)
  • fYear
    2015
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper presents the results of field measurements of touch voltages occurring in buildings under ground-fault conditions, as well as of resistance-to-ground of edifices of different nature (i.e. masonry, reinforced concrete). The goal of this experimental study was to confirm that ground-fault potential profiles and touch voltages in buildings do depend on the make-up of the structure, the floor material, the configuration and location of the grounding electrodes with respect to the point of touch, and the presence of metalwork (e.g. metal pipes) bonded to the ground system. The results of the above measurements, involving buildings of different construction type, are herein presented and discussed, and were obtained following the analytical models illustrated in Part I of this paper.
  • Keywords
    "Buildings","Voltage measurement","Electrical resistance measurement","Grounding","Concrete","Electrodes"
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Society Annual Meeting, 2015 IEEE
  • Type

    conf

  • DOI
    10.1109/IAS.2015.7356922
  • Filename
    7356922