• DocumentCode
    3715563
  • Title

    The harmonic analysis of firing delay angle based on self-power supply optical trigger 10kv high-voltage TSC device

  • Author

    Hanxing Guan; Guang Zeng

  • Author_Institution
    Department of Electric Engineering Xi´an University of Technology, China
  • fYear
    2015
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    As a conventional high-voltage reactive power compensation device, high-voltage thyristor switched capacitor (TSC) reactive power compensation device is widely used in high-voltage areas. However, when the thyristor is turned on completely, the valve terminal voltage is zero, and trigger circuit can not taken energy from the damping circuit to trigger thyristors. In order to solve the problem, the self-power supply optoelectronics trigger circuit has been a hot research. A set of device based on self-power supply photoelectric trigger 10 kv High-voltage TSC is proposed in this paper. It can delay a certain angle to achieve self-power supplying of the thyristor trigger circuit. It will result in a surge current due to the impact of voltage jumping when firing angle delay exists, which causes the trigger pulse disorder further. Therefore, in order to restrain the surge current, the reactor must be configured properly in actual. In this paper, the relationships between TSC trigger pulse delay angle and reactor and the harmonic content are analyzed according to the theory and simulation results.
  • Keywords
    "Harmonic analysis","Thyristors","Delays","Switches","Capacitors","Firing","Inductors"
  • Publisher
    ieee
  • Conference_Titel
    Future Energy Electronics Conference (IFEEC), 2015 IEEE 2nd International
  • Print_ISBN
    978-1-4799-7655-3
  • Type

    conf

  • DOI
    10.1109/IFEEC.2015.7361536
  • Filename
    7361536