DocumentCode :
3715601
Title :
PR control based cascaded current and voltage control for seamless transfer of microgrid
Author :
Kyungbae Lim;Jaeho Choi
Author_Institution :
School of Electrical Engineering, Chungbuk National University, Cheongju, Republic of Korea, 28644
fYear :
2015
Firstpage :
1
Lastpage :
6
Abstract :
This paper describes the cascaded current and voltage control for seamless transfer of microgrid with harmonic compensation according to load location. DG based microgrid is defined as a current source in the grid-connected mode and a voltage source in the islanded mode, respectively. Hence, it needs a robust control to supply the high quality power under both modes of DG based microgrid. But a connection of non-linear load and/or distorted grid can cause the system power quality degradation due to the produced non-linear current and/or voltage. Therefore, the PR control based cascaded current and voltage control which can be used under both modes simultaneously has been considered with a deliberate control topology in this paper. According to the load location, it can meet both non-linear compensation and seamless transfer between two modes. Also, a simple voltage restoration method has been added to solve the magnitude degradation of output voltage due to the practical PR control limitation and sometimes grid frequency change. Finally, proposed control methods which supply the power to the non-linear load under both grid-connected mode and islanded mode are verified through the PSIM simulation.
Keywords :
"Voltage control","Harmonic analysis","Power harmonic filters","Inverters","Microgrids","Load modeling","Current control"
Publisher :
ieee
Conference_Titel :
Future Energy Electronics Conference (IFEEC), 2015 IEEE 2nd International
Print_ISBN :
978-1-4799-7655-3
Type :
conf
DOI :
10.1109/IFEEC.2015.7361574