Comparison of Non-Detection Zone of frequency drift anti-islanding with closed-loop power controlled Distributed Generators
Author
Byeong-Heon Kim;Seung-Ki Sul
Author_Institution
Dept. of Electrical and Computer Engineering, Seoul National University, Republic of Korea
fYear
2015
Firstpage
1
Lastpage
5
Abstract
In this paper, the Non Detection Zones (NDZs) of frequency drift anti-islanding were compared according to the structure of positive feedback loop for closed-loop power controlled Distributed Generators (DGs). It was reported that the NDZ of frequency drift anti-islanding is enlarged with closed-loop based constant power controller. On the other hand, some research gives the functionality of the frequency drift anti-islanding even with the closed-loop power controller. If the principle of frequency drift is carefully considered, the positive feedback loop should be modified to maintain the performance of the conventional frequency drift anti-islanding when the cascade outer (power control) loop is constructed. And the NDZ of modified loop would not be degraded by the outer loop. In this paper, the rationale of the modification of the closed-loop is discussed. And, it is shown that the modified feedback loop doesn´t degrade the performance of the frequency drift anti-islanding with the closed-loop power controller. The performance of modification is verified by computer simulations and hardware experiments.
Keywords
"Islanding","Feedback loop","Reactive power","Frequency modulation","Frequency control","Power control","Frequency division multiplexing"
Publisher
ieee
Conference_Titel
Future Energy Electronics Conference (IFEEC), 2015 IEEE 2nd International
Print_ISBN
978-1-4799-7655-3
Type
conf
DOI
10.1109/IFEEC.2015.7361618
Filename
7361618
Link To Document