• DocumentCode
    3720339
  • Title

    High frequency interruption characteristics of VCB and its application to high voltage DC circuit breaker

  • Author

    S. Tokoyoda;M. Sato;K. Kamei;D. Yoshida;M. Miyashita;K. Kikuchi;H. Ito

  • Author_Institution
    Mitsubishi Electric Corporation, Marunouchi, Chiyoda-ku, Tokyo, Japan
  • fYear
    2015
  • Firstpage
    117
  • Lastpage
    121
  • Abstract
    High power testing methods for HV DC circuit breaker (DCCB) were investigated. Short circuit breaking tests using quasi-DC current were performed for DCCB based on the current oscillation scheme with active current injection. This DCCB has a high voltage vacuum circuit breaker as the interrupter unit. The tests were performed using two kinds of testing method (power frequency current peak method and charged reactor method) which have different breaking current waveforms. Interruption performance evaluated with the results obtained from each of the two kinds of testing method. In results, the interruption performance evaluated from these two testing method was same. Moreover, the effect of saturable reactors to the prototype DCCB was investigated in order to improve the DC current interruption performance. Due to the effect of the saturable reactors, di/dt at current zero could be decreased which makes it possible to minimize the parallel capacitance and inductance.
  • Keywords
    "Interrupters","Testing","Inductors","Plasma density","Current measurement","Inductance","Circuit breakers"
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Equipment ? Switching Technology (ICEPE-ST), 2015 3rd International Conference on
  • Type

    conf

  • DOI
    10.1109/ICEPE-ST.2015.7368353
  • Filename
    7368353