• DocumentCode
    3720369
  • Title

    The influence of electrode erosion on fault arc

  • Author

    Mei Li;Mingzhe Rong;Yi Wu;Junpeng Zhang;Yifei Wu

  • Author_Institution
    State Key Laboratory of Electrical Insulation and Power Equipment, School of Electrical Engineering, Xi´an Jiaotong University, Xi´an, China
  • fYear
    2015
  • Firstpage
    142
  • Lastpage
    145
  • Abstract
    A two-dimensional model for fault arc in a closed chamber is developed based on magnetic-hydrodynamic theory to investigate the effect of metal vapour eroded from copper electrodes on fault arc. The conservation equation for mass fraction of copper vapour is added to traditional mass, momentum and energy equations. Different energy transfer mechanisms including melting, evaporation and chemical reaction due to metal vaporization are taken into account. The distributions of temperature, pressure, mass fraction of copper vapour, pressure rise and arc voltage are simulated. Comparisons are made between the calculation results with and without electrode erosion. Results show that the presence of copper vapour has little influence on pressure rise.
  • Keywords
    "Arc discharges","Copper","Mathematical model","Plasma temperature","Cathodes"
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Equipment ? Switching Technology (ICEPE-ST), 2015 3rd International Conference on
  • Type

    conf

  • DOI
    10.1109/ICEPE-ST.2015.7368384
  • Filename
    7368384