• DocumentCode
    3723551
  • Title

    The relevance between dramatic declines of air gap breakdown voltage and fog-haze weather

  • Author

    Haiqing Niu;Tao Xu

  • Author_Institution
    School of Electric Power, South China University of Technology, Guangzhou, China
  • fYear
    2015
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The severe air pollution and fog-haze weather occurred frequently in China recent years. It is necessary to study the effect of special weather on the discharge characteristic of external insulation. In this paper, automatic discharge monitoring systems are installed in Guangzhou, a Chinese economic center and haze center, to monitor the breakdown voltage of an air gap and atmospheric parameters (such as relative humidity etc.). The research shows that the probability of dramatic declines of air gap breakdown voltage (DDAGBV) during the fog-haze weather is far more than the whole year´s, but under haze weather it much lower than the average. Combined the discharge voltage and weather parameter monitored with air quality data published by Guangzhou City Bureau of Meteorology, the reason of DDAGBV under fog-haze weather is studied. Analysis shows that the DDAGBV mainly occur under the condition of higher humidity, air quality index less than 120 (air quality is excellent, good and slight pollution). Based on the comprehensive analysis, the paper put forward that the electric field distortion rather than air pollution is the main reason of DDAGBV under the fog-haze weather.
  • Keywords
    "Monitoring","Pollution measurement","Humidity","Pollution","Electric variables measurement","Electric fields"
  • Publisher
    ieee
  • Conference_Titel
    TENCON 2015 - 2015 IEEE Region 10 Conference
  • ISSN
    2159-3442
  • Print_ISBN
    978-1-4799-8639-2
  • Electronic_ISBN
    2159-3450
  • Type

    conf

  • DOI
    10.1109/TENCON.2015.7372790
  • Filename
    7372790