DocumentCode :
3723574
Title :
Power transformer differential protection algorithm based on dead angle of Wavelet Energy Waveform
Author :
Manoj Tripathy;Neha Nirala
Author_Institution :
Department of Electrical Engineering, Indian Institute of Technology Roorkee, 247 667 (India) Uttarakhand
fYear :
2015
Firstpage :
1
Lastpage :
2
Abstract :
This paper presents a novel power transformer differential protection scheme based on dead angle of the Wavelet Energy Waveform (WEW). Distinguishing the magnetizing inrush current from internal fault current is accomplished by measuring dead angle of WEW. This scheme is investigated by using MATLAB and PSCAD/EMTDC simulation based model of a three phase, 315MVA, 220/400kV, 50Hz power transformer. The test results indicate that it can accurately detect and classify the faults with discrimination between internal fault and magnetizing inrush condition. This algorithm based differential relay (87T) is stable in case of external fault and provide precise operation even in the presence of DC offset in relaying signal.
Keywords :
"Power transformers","Surges","Surge protection","Relays","Wavelet transforms","Classification algorithms","Current measurement"
Publisher :
ieee
Conference_Titel :
TENCON 2015 - 2015 IEEE Region 10 Conference
ISSN :
2159-3442
Print_ISBN :
978-1-4799-8639-2
Electronic_ISBN :
2159-3450
Type :
conf
DOI :
10.1109/TENCON.2015.7372813
Filename :
7372813
Link To Document :
بازگشت