DocumentCode :
3732695
Title :
Reduction of common-mode current in parallel connected PV-inverters with negative grounding
Author :
Liang Zhou;Lan Wang;Zhenxing Wu;Guangsen Wang;Meina Wu
Author_Institution :
National Key Laboratory for Vessel Integrated Power System Technology, Naval University of Engineering, Wuhan, China
fYear :
2015
Firstpage :
1660
Lastpage :
1665
Abstract :
This paper is focused on the analysis and reduction of the common-mode current for parallel inverters with negative grounding in the photovoltaic (PV) generation system. Due to the existence of the solar parasitic capacitance to ground, transparent conductive oxide (TCO) corrosion occurs in some type of thin-film solar modules. The negative terminal of the thin-film array can be directly connected to the ground in a single PV-inverter to avoid TCO corrosion. However, a large common-mode current is injected when the negative terminals of parallel inverters connect to the ground directly. The performance of the proposed control strategy is verified by a PV system. The experimental results show that the performance of the proposed control strategy is as expected.
Keywords :
"Grounding","Inverters","Corrosion","Time-frequency analysis","Photovoltaic systems","Parasitic capacitance"
Publisher :
ieee
Conference_Titel :
Electrical Machines and Systems (ICEMS), 2015 18th International Conference on
Type :
conf
DOI :
10.1109/ICEMS.2015.7385307
Filename :
7385307
Link To Document :