DocumentCode
3747786
Title
The effect of a reduced power quality on the energy efficiency of stand-alone generator systems
Author
Colin Debruyne;Jan Desmet;Johan Rens;Jan De Kock
Author_Institution
Electrical Energy Laboratory (EELAB) Department of Electrical Energy, Systems and Automation (EESA) Ghent University, Sint-Pietersnieuwstraat 41, B-9000 Ghent, Belgium
fYear
2015
fDate
5/1/2015 12:00:00 AM
Firstpage
1902
Lastpage
1909
Abstract
It has already been thoroughly validated that the efficiency of direct online motors is susceptible towards certain power quality parameters such as voltage unbalance or harmonic voltage distortion. It can be assumed that electrical generators are also susceptible to these parameters, but to the author´s knowledge this effect has not yet been evaluated in scientific studies. This paper starts from the well studied additional loss mechanisms inside induction motors and consequently efforts are presented to translate these effects to stand-alone synchronous generators. Subsequently, the paper presents extensive measurements related to the effect of unbalanced and non-linear loading on the energy efficiency of 2 different 4kVA stand alone generators.
Keywords
"Harmonic analysis","Rotors","Stators","Generators","Power quality","Harmonic distortion","Loading"
Publisher
ieee
Conference_Titel
Electric Machines & Drives Conference (IEMDC), 2015 IEEE International
Type
conf
DOI
10.1109/IEMDC.2015.7409324
Filename
7409324
Link To Document