DocumentCode
3747976
Title
Interruption of fault currents due to symmetrical voltage dips near generating power plants employing doubly-fed induction generators
Author
Alejandro Marmolejo;Mirko Palazzo
Author_Institution
ABB Switzerland Ltd. Zurich, Switzerland
fYear
2015
Firstpage
84
Lastpage
89
Abstract
Variable-speed turbines have gained increasing importance in pumped-storage power plants since they present big advantages compared to the classical topology with a synchronous generator. Within the variable-speed solutions, the one employing a doubly-fed induction generator (DFIG) has become the preferred alternative for large installations since it provides the advantages of variable-speed operation and four-quadrant active and reactive power capabilities using converters rated only a small fraction of the rated power. Faults currents fed by a DFIG differ substantially from the typical current waveform fed by a synchronous generator and can impose very severe stresses for a circuit-breaker to cope with. The question whether a high-voltage circuit-breaker is capable of interrupting fault currents due to symmetrical voltage dips near pumped-storage power plants employing DFIGs is considered in the present work.
Keywords
"Circuit faults","Fault currents","Voltage fluctuations","Short-circuit currents","Rotors","Power generation","Integrated circuit modeling"
Publisher
ieee
Conference_Titel
Energy Conversion (CENCON), 2015 IEEE Conference on
Type
conf
DOI
10.1109/CENCON.2015.7409518
Filename
7409518
Link To Document