• DocumentCode
    3747976
  • Title

    Interruption of fault currents due to symmetrical voltage dips near generating power plants employing doubly-fed induction generators

  • Author

    Alejandro Marmolejo;Mirko Palazzo

  • Author_Institution
    ABB Switzerland Ltd. Zurich, Switzerland
  • fYear
    2015
  • Firstpage
    84
  • Lastpage
    89
  • Abstract
    Variable-speed turbines have gained increasing importance in pumped-storage power plants since they present big advantages compared to the classical topology with a synchronous generator. Within the variable-speed solutions, the one employing a doubly-fed induction generator (DFIG) has become the preferred alternative for large installations since it provides the advantages of variable-speed operation and four-quadrant active and reactive power capabilities using converters rated only a small fraction of the rated power. Faults currents fed by a DFIG differ substantially from the typical current waveform fed by a synchronous generator and can impose very severe stresses for a circuit-breaker to cope with. The question whether a high-voltage circuit-breaker is capable of interrupting fault currents due to symmetrical voltage dips near pumped-storage power plants employing DFIGs is considered in the present work.
  • Keywords
    "Circuit faults","Fault currents","Voltage fluctuations","Short-circuit currents","Rotors","Power generation","Integrated circuit modeling"
  • Publisher
    ieee
  • Conference_Titel
    Energy Conversion (CENCON), 2015 IEEE Conference on
  • Type

    conf

  • DOI
    10.1109/CENCON.2015.7409518
  • Filename
    7409518