DocumentCode
3748024
Title
Improved DPWM scheme for improvement of grid current quality in a large-scale grid-connected inverter system with a LCL-filter
Author
Jin-Hyuk Park;Kyo-Beum Lee
Author_Institution
Division of Electrical and Computer Engineering, Ajou University, Suwon, South Korea
fYear
2015
Firstpage
343
Lastpage
348
Abstract
This paper proposes an improved discontinuous PWM (DPWM) method in a grid-connected inverter system. When the conventional 60° DPWM is used in the switching method, the output voltage of the inverter has many harmonics compared to the continuous PWM (CPWM) switching method. In large-scale system, a LCL-filter cannot sufficiency reduce the harmonics of the inverter output voltage. If these harmonics and the resonance frequency band caused by a grid-connected LCL-filter are overlapped, the grid current oscillates. To solve this problem, the proposed method continuously changes the discontinuous modulation signal by injecting triangular wave to modulation signal. The proposed algorithm can reduce the harmonics of inverter output voltage. The proposed DPWM is verified from PSIM simulation with a 600-kW 2-level grid-connected inverter system.
Publisher
ieee
Conference_Titel
Energy Conversion (CENCON), 2015 IEEE Conference on
Type
conf
DOI
10.1109/CENCON.2015.7409566
Filename
7409566
Link To Document