Grid connected high power medium voltage wind energy conversion system with reduced line harmonics
Author
M.S. Hamad;K.H. Ahmed;Ayman S. Abdel-Khalik
Author_Institution
Electrical and Control Eng. Dept., Arab Academy for Science and Technology, Alexandria, Egypt
fYear
2015
Firstpage
1279
Lastpage
1284
Abstract
Conventional high power medium voltage wind energy conversion systems utilize 12-pulse converter, integrated with Y/Y/Δ front-end transformer for grid interconnection. Fairly accepted performance can be achieved even by operating the 12-pulse converter using an optimized power locus for power factor improvement. In this paper, an active filter topology is proposed using only one shunt active power filter and tapped front-end transformer. The proposed topology features are simple configuration, less complexity, reduced components, and optimized compensation current requirement as it benefits from the front-end transformer´s natural mitigation of the harmonic currents. In addition to simulation, a low voltage scaled prototype is built to experimentally validate the proposed topology effectiveness.
Keywords
"Power harmonic filters","Harmonic analysis","Active filters","Topology","Integrated circuits","Prototypes","Renewable energy sources"