• DocumentCode
    3758193
  • Title

    High performance parallel single-phase converter reconfiguration for enhanced availability

  • Author

    Mohammad H. Hedayati;Vinod John

  • Author_Institution
    Indian Institute of Science (IISc), Bangalore 560012, India
  • fYear
    2015
  • Firstpage
    52
  • Lastpage
    57
  • Abstract
    Paralleling power converters is a common practice in industries to enhance total power rating, reliability, and availability of the system. In case of fault occurring in systems with parallel converters, the faulty power converter can be isolated and the system can still be operated at reduced power level. In this paper, a grid-connected power converter consisting of two parallel H-bridge converter, with low ground leakage current, is considered. Two contingency configurations, that are also of low ground leakage current, are proposed to enhance the availability of the system. This is done by reconfiguring the power circuit to a single H-bridge, in the case of failure of the other bridge. The power converter is experimentally tested with the proposed configurations for experimental validation. The results show that, the second configuration has better performance in terms of power loss and current THD.
  • Keywords
    "Circuit faults","Inductors","Leakage currents","Switches","Pulse width modulation","Switching circuits","Topology"
  • Publisher
    ieee
  • Conference_Titel
    Electrical Machines & Power Electronics (ACEMP), 2015 Intl Conference on Optimization of Electrical & Electronic Equipment (OPTIM) & 2015 Intl Symposium on Advanced Electromechanical Motion Systems (ELECTROMOTION), 2015 Intl Aegean Conference on
  • Type

    conf

  • DOI
    10.1109/OPTIM.2015.7426986
  • Filename
    7426986