• DocumentCode
    3758843
  • Title

    Research on step voltage of medium voltage shore power system near fault location

  • Author

    Yang Feng;Luo Ningzhao;Huang Jing;Wu Benxiang

  • Author_Institution
    Electrical Engineering College, Naval University of Engineering, Wuhan, China
  • fYear
    2015
  • Firstpage
    1005
  • Lastpage
    1009
  • Abstract
    The step voltage carried on by personnel is researched when single-phase grounding fault of medium voltage shore power system occurs. The experiments are designed to measure resistance value from the coastline to the ground point and the resistivity of sea water. According to the data obtained from experiments, the finite element model is established though ANSYS, the potential distribution from the hull to the fault point is calculated when single-phase fault of medium voltage shore power system occurs, and the decay of surface potential in the wharf is obtained, especially drop speed of potential near the point of failure is paid close attention, the safety range of step voltage to terminal staffs is obtained.
  • Keywords
    "Erbium","Decision support systems","Electrical resistance measurement","Q measurement","Resistance","Grounding","Ammeters"
  • Publisher
    ieee
  • Conference_Titel
    Advanced Information Technology, Electronic and Automation Control Conference (IAEAC), 2015 IEEE
  • Print_ISBN
    978-1-4799-1979-6
  • Type

    conf

  • DOI
    10.1109/IAEAC.2015.7428708
  • Filename