DocumentCode
3758843
Title
Research on step voltage of medium voltage shore power system near fault location
Author
Yang Feng;Luo Ningzhao;Huang Jing;Wu Benxiang
Author_Institution
Electrical Engineering College, Naval University of Engineering, Wuhan, China
fYear
2015
Firstpage
1005
Lastpage
1009
Abstract
The step voltage carried on by personnel is researched when single-phase grounding fault of medium voltage shore power system occurs. The experiments are designed to measure resistance value from the coastline to the ground point and the resistivity of sea water. According to the data obtained from experiments, the finite element model is established though ANSYS, the potential distribution from the hull to the fault point is calculated when single-phase fault of medium voltage shore power system occurs, and the decay of surface potential in the wharf is obtained, especially drop speed of potential near the point of failure is paid close attention, the safety range of step voltage to terminal staffs is obtained.
Keywords
"Erbium","Decision support systems","Electrical resistance measurement","Q measurement","Resistance","Grounding","Ammeters"
Publisher
ieee
Conference_Titel
Advanced Information Technology, Electronic and Automation Control Conference (IAEAC), 2015 IEEE
Print_ISBN
978-1-4799-1979-6
Type
conf
DOI
10.1109/IAEAC.2015.7428708
Filename
7428708
Link To Document