DocumentCode :
3760254
Title :
Identification and coping approaches of sympathetic inrush current based on the station-area information of smart substation
Author :
Yi Wang;Xuanwei Qi;Xianggen Yin;Zhe Zhang;Li Gan
Author_Institution :
Electric Power Research Institute of Guangdong Power Grid Corporation Guangzhou, Guangdong Province, China, 510080
fYear :
2015
Firstpage :
1020
Lastpage :
1024
Abstract :
Due to the absence of the effective identification and coping approaches of the sympathetic inrush current, the mal-operation of differential protection may be occasionally caused by sympathetic inrush current. In order to address this issue, the features of the sympathetic inrush current and the influence of the sympathetic inrush current on the differential protection are analyzed in detail in this paper. It is discovered that the second harmonic phase angle difference between the inrush current and the sympathetic inrush current are nearly 180°. Based on this, an identification and coping approaches for the sympathetic inrush current utilizing the information sharing between the smart substations is proposed in this paper. The effectiveness of this method is validated by the digital simulation and dynamic model experiment.
Keywords :
"Surges","Surge protection","Power transformers","Decision support systems","Harmonic analysis","Substations","Integrated circuits"
Publisher :
ieee
Conference_Titel :
Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
Type :
conf
DOI :
10.1109/DRPT.2015.7432380
Filename :
7432380
Link To Document :