    Analysis on single-phase line break fault of 10kV non-grounded distribution network

  • Author

    Rui Wang;Wei Cong;Qibao Kang;Guoqiang Liu;Hui Wang;Ruipeng Yi

  • Author_Institution
    Key Laboratory of Power Systemm Intelligent Dispatch and Control, Shandong University, Jinan, Shandong Province, China
  • fYear
    2015
  • Firstpage
    1043
  • Lastpage
    1049
  • Abstract
    Line break fault is becoming more and more frequent in 10kV neutral point non-grounded distribution system. This paper takes 10kV distribution line single-phase line break fault as the research object, analyzes the characteristics of electrical quantities when single-phase line break fault occurs, including single-phase line break without grounding point, single-phase line break with grounding at power supply side and single-phase line break with grounding at load side. Electrical quantities during single-phase line break fault are analyzed using symmetrical component method with sequence network and vector diagram, the variation of electrical quantities are summarized, and protection criterion for single-phase line break fault is proposed. Simulation results by PSCAD/EMTDC ensure the correctness of the analysis results and line break protection criterion.