DocumentCode
3760258
Title
Analysis on single-phase line break fault of 10kV non-grounded distribution network
Author
Rui Wang;Wei Cong;Qibao Kang;Guoqiang Liu;Hui Wang;Ruipeng Yi
Author_Institution
Key Laboratory of Power Systemm Intelligent Dispatch and Control, Shandong University, Jinan, Shandong Province, China
fYear
2015
Firstpage
1043
Lastpage
1049
Abstract
Line break fault is becoming more and more frequent in 10kV neutral point non-grounded distribution system. This paper takes 10kV distribution line single-phase line break fault as the research object, analyzes the characteristics of electrical quantities when single-phase line break fault occurs, including single-phase line break without grounding point, single-phase line break with grounding at power supply side and single-phase line break with grounding at load side. Electrical quantities during single-phase line break fault are analyzed using symmetrical component method with sequence network and vector diagram, the variation of electrical quantities are summarized, and protection criterion for single-phase line break fault is proposed. Simulation results by PSCAD/EMTDC ensure the correctness of the analysis results and line break protection criterion.
Keywords
"Grounding","Decision support systems","Power supplies","Impedance","Power industry","Simulation","Analytical models"
Publisher
ieee
Conference_Titel
Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
Type
conf
DOI
10.1109/DRPT.2015.7432384
Filename
7432384