DocumentCode
3760365
Title
The study on the partial discharge and insulation aging detection of cable based on the chaotic characteristic parameter
Author
Tao Liu;Lixing Zhou
Author_Institution
Changsha University of Science and Technology, ChangSha, China
fYear
2015
Firstpage
1637
Lastpage
1642
Abstract
Partial discharge (PD) and water tree is the important reason to insulation deterioration of XLPE cable, So PD monitoring and locating is an important means of cable operation and maintenance. On the basis of the mechanism of cable´s PD and the research of cable aging diagnosis, the Matlab Simulink simulation model of XLPE is built, and the variation law of the chaotic characteristic parameters of PD signal is studied. The simulation results show that: with the increase of transmission distance, the correlation dimension decreases with the decreasing of the logarithmic function, and the new method based on chaotic characteristic is proposed.
Keywords
"Partial discharges","Voltage measurement","Cable insulation","Voltage control","Aging","Correlation","Q measurement"
Publisher
ieee
Conference_Titel
Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
Type
conf
DOI
10.1109/DRPT.2015.7432495
Filename
7432495