DocumentCode
3760402
Title
Research of VFTO in 110kV minimized GIS
Author
He Qifei;Hao Zhiguo;Guo Jie
Author_Institution
Xi´an Jiaotong University, Institute of Electrical Engineering, Xi´an, Shaanxi
fYear
2015
Firstpage
1786
Lastpage
1789
Abstract
110kV minimized gas insulated substation (GIS) has been widely used in China, due to its great electrical properties. The closing or opening operation of disconnector switches (DS) and circuit breaker (CB), and single-phase ground fault are all probable to cause the very fast transient overvoltage (VFTO), which is a threat to the power system. Compared to the structure of higher voltage GIS, three-phase electrical equipment in 110kV minimized GIS is placed in the same box. So we must establish the three-phase model of GIS and then calculate its VFTO. This paper referred to 110 kV minimized GIS power system. Using the Electro-magnetic Transient Program (EMTP), numerical simulation and analysis of VFTO in different DS, CB operation modes and single-phase grounding fault were carried out. And the data of VETO under different operation modes, including the frequency, amplitude, steepness and waveform were obtained. Then it calculated and analyzed the influence on VFTO of length of branch bus and transformer entrance capacitance, in order to provide reference basis to the structure design of GIS and analysis of VFTO.
Keywords
"Gas insulation","Decision support systems","Circuit breakers","Transient analysis","Substations","Switches"
Publisher
ieee
Conference_Titel
Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
Type
conf
DOI
10.1109/DRPT.2015.7432532
Filename
7432532
Link To Document