DocumentCode :
3762930
Title :
Wide Area backup protection using weighted apparent impedance
Author :
Pratim Kundu;Ashok Kumar Pradhan
Author_Institution :
Department of Electrical Engineering, Indian Institute of Technology Kharagpur, India
fYear :
2015
Firstpage :
675
Lastpage :
679
Abstract :
Identification of the faulted line in a system can improve the performance of backup protection schemes. This paper presents a Wide Area Measurement System (WAMS) based algorithm, where voltage and current signals from synchrophasors placed at strategic locations are used for the identification of faulted line. Conventional backup protection schemes require complex setting and they maloperate under flow transfer which can be avoided using the proposed method. The studies performed on the 39-bus New-England system using data simulated through EMTDC/PSCAD validate accuracy of the proposed algorithm.
Keywords :
"Fault diagnosis","Indexes","Impedance","Relays","Power measurement","Power systems","Weight measurement"
Publisher :
ieee
Conference_Titel :
Power, Communication and Information Technology Conference (PCITC), 2015 IEEE
Type :
conf
DOI :
10.1109/PCITC.2015.7438082
Filename :
7438082
Link To Document :