DocumentCode :
3763319
Title :
Metrological frequency response analysis of a high current instrument transformer
Author :
Christian J?schke;Peter Schegner
Author_Institution :
Technische Universit?t Dresden, Germany
fYear :
2015
Firstpage :
640
Lastpage :
645
Abstract :
This paper presents the metrological frequency response analysis of a high current instrument transformer (HCT) with a rated primary current of 8 kA. A special measuring system is used to identify the frequency response of the HCT at different primary currents in a frequency range up to 40 kHz. The burden dependency of the frequency response is determined by using different resistive and resistive-inductive burdens. The measuring results indicate the good transmission behaviour of the HCT at higher frequencies by applying resistive burdens. However, resonances occur by applying resistive-inductive burdens, resulting in high resonance peaks which deteriorate the transmission behaviour of the HCT and cause high voltages at its secondary side.
Keywords :
"Ribs","Current measurement","Instrument transformers","Couplings","Resonant frequency"
Publisher :
ieee
Conference_Titel :
Sensing Technology (ICST), 2015 9th International Conference on
Electronic_ISBN :
2156-8073
Type :
conf
DOI :
10.1109/ICSensT.2015.7438476
Filename :
7438476
Link To Document :
بازگشت