DocumentCode :
3765693
Title :
Study on the anti-islanding protection performance test for photovoltaic inverter based on digital/physical hybrid simulation
Author :
Fei Zheng;Xiaodi Qin;Xiaolin Zhang;Jingsheng Huang;Junjun Zhang
Author_Institution :
China Electric Power Research Institute, Nanjing, China, 210003
fYear :
2015
Firstpage :
1
Lastpage :
4
Abstract :
A modeling and testing scheme for photovoltaic grid-connected inverter anti-islanding protection performance based on RT-LAB simulator is proposed. First, the model of power loop of grid-connected PV inverter anti-islanding protection test is established, which contains PV array model, photovoltaic inverter power circuit model, anti-islanding protection performance testing device model and grid model; Then signal conditioning module model is built, the I/O physical interface circuit is constructed which connects the controller board of photovoltaic inverter and RT-LAB simulator. Finally, according to national standard GB/T 29319-2012 “Technical requirements for connecting photovoltaic power system to distribution network”, anti-islanding protection performance testing for the real control board of 125kVA photovoltaic inverter, and the test result can fully reflect dynamic and static performance in the process of anti-islanding protection performance test, and prove that the anti-islanding protection performance test scheme based on digital/physical hybrid simulation is effective.
Publisher :
iet
Conference_Titel :
Renewable Power Generation (RPG 2015), International Conference on
Print_ISBN :
978-1-78561-040-0
Type :
conf
DOI :
10.1049/cp.2015.0517
Filename :
7446674
Link To Document :
بازگشت