• DocumentCode
    3765717
  • Title

    Research on synchronization test method for distributed sampling data based on precise time-setting

  • Author

    Bu Qiangsheng;Liu Yu;Lin Jinjiao;Huang Haosheng;Song Liangliang

  • Author_Institution
    State Grid Jiangsu Electric Power Company Research Institute, Nanjing, Jiangsu, China
  • fYear
    2015
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Synchronous sampling data is considered as a basic condition for correct operation of all kinds of differential protections in a substation. It is necessary to test it in the substation commissioning procedure. This paper first addresses the root causes of synchronization problems and the necessity of onsite synchronization test for line differential protections and all distributed sampling differential protections in a smart substation. Then a method based on precise time-setting is proposed to test sampling synchronization of differential protections, which can solve difficulties of on-site synchronization test of distributed electrical data. Specific implementations are given and the causes of error are also analyzed in this paper. In a real 500kV smart substation project, error of data synchronization is controlled under 1.5 ° by testing line differential protections and the whole sampling circuit based on the method, which entirely meets the performance requirements of differential protections.
  • Publisher
    iet
  • Conference_Titel
    Renewable Power Generation (RPG 2015), International Conference on
  • Print_ISBN
    978-1-78561-040-0
  • Type

    conf

  • DOI
    10.1049/cp.2015.0542
  • Filename
    7446699