DocumentCode :
3767084
Title :
Influence of corona intensity on the hydropobhicity recovery of polymeric insulating samples
Author :
Shakthi Prasad D; Subba Reddy B;Alok R Verma;Desik Rengarajan;Veeresh N Patil
Author_Institution :
High Voltage Laboratory, Dept. of Electrical Engg., Indian Institute of Science, Bangalore, India
fYear :
2015
Firstpage :
61
Lastpage :
65
Abstract :
Corona discharges from the insulator metal parts and the line hardware influence long term performance of the silicon rubber insulators used in HVAC and HVDC transmission. Polymeric insulators when installed are highly hydrophobic; they have to perform under various mechanical, electrical and environmental stresses, over a period the hydrophobic properties decrease. The present work, investigates the loss and recovery of hydrophobicity of silicon rubber insulator samples exposed to AC and DC corona. Two types of specially designed corona generating electrodes are used to simulate uniform and non-uniform corona stress on the samples. A systematic study of loss and recovery of hydrophobicity as a function of electric field intensity and type of voltage employed is conducted. The investigation shows that the effect of DC corona on hydrophobicity property is significantly low in comparison with that of AC corona. The initial rate of recovery of hydrophobicity is found to be higher and stabilized over a period of time.
Keywords :
"Corona","Electrodes","Insulators","Electric fields","Polymers","Surface discharges","Surface treatment"
Publisher :
ieee
Conference_Titel :
Condition Assessment Techniques in Electrical Systems (CATCON), 2015 International Conference on
Type :
conf
DOI :
10.1109/CATCON.2015.7449509
Filename :
7449509
Link To Document :
بازگشت