Performance of 230 kV transmission lines applying externally gapped type arresters
Author :
Hernández-Corona, Ramiro ; Regalado-Contreras, Gustavo
Author_Institution :
Dept. of Transmission & Distribution, Electr. Res. Inst., Temixco, Mexico
Volume :
1
fYear :
2001
fDate :
2001
Firstpage :
339
Abstract :
The paper presents the model developed by the Alternative Transients Program (ATP) in order to simulate the performance of a 230 kV Mexican transmission line with externally gapped type arresters installed in all three phases of some towers of the line studied. The results obtained from the model helped to determine the countermeasure to reduce lightning faults in the Mexican transmission line by installing arresters with arcing horn gap
Keywords :
arresters; lightning protection; power overhead lines; power transmission protection; 230 kV; Alternative Transients Program; Mexican transmission line; arcing horn gap; externally gapped type arresters; lightning faults reduction; performance simulation; towers; Arresters; Insulation; Lightning; Poles and towers; Power system transients; Solid modeling; Switches; Transmission lines; Voltage; Zinc oxide;