DocumentCode :
3767898
Title :
Simulation analysis of transformer inrush current based on the same switching angle
Author :
Guo Zheng Qi;Zhi Zhen Liu;Yong Yang;Wei Ping Liao
Author_Institution :
School of Electrical Engineering, Shandong University, Jinan 250061, China
fYear :
2015
Firstpage :
76
Lastpage :
77
Abstract :
High-magnitude inrush current happens when the no-load transformer core falls into saturation during energization. A new method of suppressing the inrush current from a three-phase transformer is proposed based on the principle of the same switching angle. The closing time of transformer is obtained by the actual opening time. The results of simulation show that the size of the synthesized magnetic flux is closely related to the synthetic voltage and the inrush current of each phase is closely related to its flux. The strategy completely eliminates the transient flux, and then the transformer runs directly in the steady state.
Keywords :
"Surges","Surge protection","Phase transformers","Circuit faults","Switches","Transient analysis","Remanence"
Publisher :
ieee
Conference_Titel :
Applied Superconductivity and Electromagnetic Devices (ASEMD), 2015 IEEE International Conference on
Print_ISBN :
978-1-4673-8106-2
Type :
conf
DOI :
10.1109/ASEMD.2015.7453474
Filename :
7453474
Link To Document :
بازگشت